NA2XY 5 x (10-50) mm² 0.6/1 kV

Al / XLPE / PVC
(Aluminium Conductor, XLPE Insulated, PVC Sheathed)
Standard Specification : SNI IEC 60502-1 : 2009

Application

Power cable : Indoors, cable trunking, outdoors
and burried in the ground, for power stations,
industry and switchgear as well as for urban
supply networks, if mechanical damage is
unlikely.


Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated

Note :
Conductor Shape
10 - 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 50 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
10 - 50 sqmm supplied in wooden drum @ 1000 m
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
10
21.5 521
16
24.5 709
25
27.5 935
35
31.0 1,187
50
36.0 1,479

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
10 3.08 3.949 0.248 65 70 0.94
16 1.91 2.449 0.236 88 92 1.50
25 1.20 1.539 0.242 117 118 2.35
35 0.868 1.113 0.234 144 143 3.29
50 0.641 0.822 0.232 176 168 4.70

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information