NA2XY 4 x (10-300) mm² 0.6/1 kV

Al / XLPE / PVC
(Aluminium Conductor, XLPE Insulated, PVC Sheathed)
Standard Specification : SNI IEC 60502-1 : 2009

Application

Power cable : Indoors, cable trunking, outdoors
and burried in the ground, for power stations,
industry and switchgear as well as for urban
supply networks, if mechanical damage is
unlikely.


Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated

Note :
Conductor Shape
10 - 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor

Standard Packing
10 - 120 sqmm supplied in wooden drum @ 1000 m
150 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
10 19.5 446
16 23.0 601
25 25.5 787
35 28.5 994
50 32.5 1,058
70 36.5 1,431
95 40.5 1,820
120 45.5 2,275
150 51.5 2,749
185 56.0 3,336
240 62.5 4,243
300 68.0 5,131

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
10 3.08 3.949 0.248 63 69 0.94
16 1.91 2.449 0.236 85 90 1.50
25 1.20 1.539 0.242 112 116 2.35
35 0.868 1.113 0.234 139 140 3.29
50 0.641 0.822 0.232 164 162 4.70
70 0.443 0.568 0.229 206 197 6.58
95 0.320 0.411 0.224 253 237 8.93
120 0.253 0.325 0.223 295 269 11.28
150 0.206 0.265 0.225 343 305 14.10
185 0.164 0.211 0.225 393 344 17.39
240 0.125 0.162 0.223 466 399 22.56
300 0.100 0.130 0.222 537 451 28.20

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information