NAYY 5 x (10-50) mm2 0.6/1 kV

Al / PVC / PVC

(Aluminium Conductor, PVC Insulated, PVC Sheathed)
Standard Specification : SNI IEC 60502-1 : 2009

Application

Power cable : Indoors, cable trunking, outdoors
and burried in the ground, for power stations,
industry and switchgear as well as for urban
supply networks, if mechanical damage is unlikely.


Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Heat Resistance
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated

Note :
Conductor Shape
10 - 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 50 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
10 - 50 sqmm supplied in wooden drum @ 1000 m
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
10
23.0 636
16
26.5 847
25
29.5 1,098
35
33.0 1,389
50
38.0 1,731

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 70°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
10
3.08 3.701 0.269 54 60 0.76
16
1.91 2.295 0.253 73 78 1.22
25
1.20 1.442 0.257 97 101 1.90
35
0.868 1.043 0.247 120 121 2.66
50
0.641 0.771 0.247 147 144 3.80

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information