NAYY 3 x (10-300) mm² 0.6/1 kV

Al / PVC / PVC

(Aluminium Conductor, PVC Insulated, PVC Sheathed)
Standard Specification : SNI IEC 60502-1 : 2009

Application

Power cable : Indoors, cable trunking, outdoors
and burried in the ground, for power stations,
industry and switchgear as well as for urban
supply networks, if mechanical damage is unlikely.


Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Heat Resistance
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated

Note :
Conductor Shape
10 - 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor

Standard Packing
10 - 150 sqmm supplied in wooden drum @ 1000 m
185 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
10
19.4
459
16
22.5 601
25
24.5 767
35
27.5 952
50
30.0 986
70
34.0 1,301
95
38.5 1,682
120
41.5 1,973
150
46.0 2,399
185
50.5 2,936
240
57.0 3,741
300
62.5 4,534

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 70°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
10
3.08
3.701
0.269
46
52
0.76
16
1.91 2.295
0.253 62 69 1.22
25
1.20 1.442 0.257 81 88 1.90
35
0.868 1.043 0.247 100 106 2.66
50
0.641 0.770
0.247
126
131
3.80
70
0.443 0.533
0.238 158 160
5.32
95
0.320
0.385
0.238
194
192
7.22
120
0.253 0.305 0.233 225 219 9.12
150
0.206 0.248 0.235 257 245 11.40
185
0.164 0.198 0.233 297 278 14.06
240
0.125 0.152 0.232 352 322 18.24
300
0.100 0.122 0.231 405 364 22.80

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information