NAYA 10 - 400 mm² 450/750 V

Al / PVC

(Aluminium Conductor, PVC Insulated)
Adapted Specifcation : IEC 60227-1 : 2007 ; IEC 60228 : 2004

Application

For building wire installed in conduit in dry
location, sometimes can be used as grounding
conductor, inherently fame retardant in
compliance with IEC 60332-1.

Special Features on Request
• Oil Resistance
• Flame Retardant Cat. A, B, C
• Heat Resistance
• Nylon Coated


Note :
Conductor Shaped
10 - 400 sqmm supplied in non compacted circular stranded (rm) conductor shape

Standard Packing
10 - 400 sqmm supplied in wooden drum @1000 m
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
10 6.2 54
16 7.3 77
25 9.0 117
35 10.1 153
50 12.2 210
70 13.7 271
95 16.0 374
120 17.7 452
150 19.7 559
185 22.0 696
240 25.1 903
300 27.9 1,119
400 31.3 1,410

Electrical Data

Conductor Insulation Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 70°C
Insulation
Resistance
at 70°C
in pipe in air
(mm²)
Max. (Ω/km)
Max. (Ω/km)
Min.
(M.Ω.km)
(mH/km) Max. (A) Max. (A) Max. (kA)
10 3.08 3.701 0.0065 0.274 35 57 0.76
16 1.91 2.295 0.0050 0.258 48 77 1.22
25 1.20 1.442 0.0050 0.257 65 101 1.90
35 0.868 1.043 0.0040 0.249 80 123 2.66
50 0.641 0.771 0.0045 0.248 103 154 3.80
70 0.443 0.533 0.0035 0.239 129 191 5.32
95 0.320 0.385 0.0035 0.239 162 226 7.22
120 0.253 0.305 0.0032 0.235 184 269 9.12
150 0.206 0.249 0.0032 0.235 - 305 11.40
185 0.164 0.199 0.0032 0.235 - 348 14.06
240 0.125 0.152 0.0032 0.233 - 410 18.24
300 0.100 0.123 0.0030 0.232 - 473 22.80
400 0.0778 0.097 0.0028 0.229 - 566 30.40

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information