NA2XSY 1 x (10-800) mm² 0.6/1 kV

Al / XLPE / CTS / PVC
(Aluminium Conductor, XLPE Insulated, Copper Tape Screen, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For power plants and switchgear as well as
for installation of sub-station; for installation
indoors in confinned spaces and cable channels
because of small bending radius. As burried
cable, because of its light weight prefered in
where installation is difficult.


Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated

Note :
Conductor Shape
10 - 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 800 sqmm supplied in non compacted circular stranded (rm) or compacted circular stranded (cm) conductor shape

Standard Packing
10 - 630 sqmm supplied in wooden drum @ 1000 m
800 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx. approx.
mm² mm kg/km
10 11.1 160
16 12.3 199
25
13.9 255
35 15.1 305
50 16.8 380
70 18.9 475
95 21.0 571
120 22.5 658
150 25.0 805
185 27.0 954
240 30.0 1,188
300 32.5 1,404
400
38.5 1,961
500 41.5 2,268
630 45.5 2,791
800 50.5 3,436

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
Trefoil formation
Flat formation
in air in ground in air in ground
(mm²) Max. (Ω/km) Max. (Ω/km) (mH/km) (mH/km) Max. (A) Max. (A) Max. (A) Max. (A) Max. (kA)
10 3.08 3.949 0.390 0.437 64 69 66 72 0.94
16 1.91 2.449 0.360 0.406 86 90 89 94 1.50
25
1.20 1.539 0.344 0.390 115 117 118 120 2.35
35 0.868 1.113 0.327 0.373 140 140 144 144 3.29
50 0.641 0.822 0.313 0.360 171 166 176 171 4.70
70 0.443 0.568 0.300 0.346 217 204 224 210 6.58
95 0.320 0.411 0.288 0.335 266 244 274 251 8.93
120 0.253 0.325 0.283 0.330 308 278 317 285 11.28
150 0.206 0.265 0.277 0.323 357 313 368 321 14.10
185 0.164 0.211 0.273 0.320 414 355 426 364 17.39
240 0.125 0.162 0.266 0.312 496 413 511 423 22.56
300 0.100 0.130 0.261 0.307 573 467 590 477 28.20
400
0.0778 0.102 0.258 0.304 687 537 706 549 37.60
500 0.0605 0.081 0.256 0.303 793 609 814 621 47.00
630 0.0469 0.064 0.253 0.299 923 691 947 704 59.22
800 0.0367 0.052 0.251 0.298 1060 775 1084 787 75.20

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information