NA2XFGbY 2 x (10-300) mm² 0.6/1 kV

Al / XLPE / SFWA / PVC
(Aluminium Conductor, XLPE Insulated, Galvanized Steel Flat Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For installation in the ground, indoors, cable
trunking and outdoors if increased mechanical
protection is required or where high-pulling
stresses may occur during installation or
operation.


Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen

Note :
Conductor Shape
10 - 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
10 - 150 sqmm supplied in wooden drum @ 1000 m
185 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx. approx.
mm² mm kg/km
10 18.8 662
16 21.5 804
25 24.0 986
35 26.0 1,187
50 29.5 1,375
70 33.5 1,711
95 37.5 2,125
120 41.0 2,489
150 44.0 2,876
185 50.5 3,552
240 55.0 4,263
300 60.5 5,106

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²) Max. (Ω/km) Max. (Ω/km) (mH/km) Max. (A) Max. (A) Max. (kA)
10 3.08 3.949 0.248 70 77 0.94
16 1.91 2.449 0.236 95 102 1.50
25 1.20 1.539 0.242 123 130 2.35
35 0.868 1.113 0.234 151 157 3.29
50 0.641 0.822 0.232 184 186 4.70
70 0.443 0.568 0.229 232 229 6.58
95 0.320 0.411 0.224 284 274 8.93
120 0.253 0.325 0.223 329 312 11.28
150 0.206 0.265 0.225 371 347 14.10
185 0.164 0.211 0.225 432 394 17.39
240 0.125 0.162 0.223 509 457 22.56
300 0.100 0.130 0.222 583 515 28.20

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information