NA2XFGbY 3 x (10-300) mm² 0.6/1 kV

Al / XLPE / SFWA / PVC
(Aluminium Conductor, XLPE Insulated, Galvanized Steel Flat Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For installation in the ground, indoors, cable
trunking and outdoors if increased mechanical
protection is required or where high-pulling
stresses may occur during installation or
operation.


Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen

Note :
Conductor Shape
10 - 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor

Standard Packing
10 - 150 sqmm supplied in wooden drum @ 1000 m
185 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
10 19.7 702
16 22.5 887
25 25.0 1,093
35 27.5 1,318
50 30.0 1,382
70 34.5 1,770
95 37.5 2,130
120 41.0 2,488
150 46.0 2,976
185 50.5 3,533
240 56.0 4,327
300 61.0 5,127

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
10 3.08 3.949 0.248 59 65 0.94
16 1.91 2.449 0.236 80 85 1.50
25 1.20 1.539 0.242 105 109 2.35
35 0.868 1.113 0.234 129 132 3.29
50 0.641 0.822 0.232 160 160 4.70
70 0.443 0.568 0.229 201 195 6.58
95 0.320 0.411 0.224 246 234 8.93
120 0.253 0.325 0.223 286 266 11.28
150 0.206 0.265 0.225 326 297 14.10
185 0.164 0.211 0.225 378 338 17.39
240 0.125 0.162 0.223 447 391 22.56
300 0.100 0.130 0.222 513 442 28.20

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information