NA2XFGbY 4 x (10-300) mm² 0.6/1 kV

Al / XLPE / SFWA / PVC
(Aluminium Conductor, XLPE Insulated, Galvanized Steel Flat Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For installation in the ground, indoors, cable
trunking and outdoors if increased mechanical
protection is required or where high-pulling
stresses may occur during installation or
operation.


Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen

Note :
Conductor Shape
10 - 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor

Standard Packing
10 - 120 sqmm supplied in wooden drum @ 1000 m
150 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
10 21.5 797
16 24.5 1,010
25 27.0 1,253
35 30.0 1,517
50 34.0 1,678
70 38.5 2,142
95 42.5 2,623
120 47.5 3,169
150 53.5 3,767
185 57.5 4,421
240 64.5 5,471
300 70.0 6,483

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
10 3.08 3.949 0.248 65 71 0.94
16 1.91 2.449 0.236 88 92 1.50
25 1.20 1.539 0.242 117 119 2.35
35 0.868 1.113 0.234 144 143 3.29
50 0.641 0.822 0.232 169 164 4.70
70 0.443 0.568 0.229 211 200 6.58
95 0.320 0.411 0.224 259 240 8.93
120 0.253 0.325 0.223 301 272 11.28
150 0.206 0.265 0.225 350 307 14.10
185 0.164 0.211 0.225 400 347 17.39
240 0.125 0.162 0.223 474 402 22.56
300 0.100 0.130 0.222 544 454 28.20

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information