NA2XY 3 x (10-300) mm² 0.6/1 kV

Al / XLPE / PVC
(Aluminium Conductor, XLPE Insulated, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

Power cable : Indoors, cable trunking, outdoors
and burried in the ground, for power stations,
industry and switchgear as well as for urban
supply networks, if mechanical damage is
unlikely.


Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated

Note :
Conductor Shape
10 - 16 sqmm supplied in non compacted circular stranded (rm) conductor shap
25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor

Standard Packing
10 - 185 sqmm supplied in wooden drum @ 1000 m
240 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
10 18.0 382
16 21.0 510
25 23.5 660
35 26.0 830
50 28.0 828
70 32.5 1,126
95 36.0 1,422
120 39.0 1,716
150 44.0 2,113
185 48.5 2,577
240 54.5 3,279
300 59.0 3,963

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
10 3.08 3.949 0.248 57 63 0.94
16 1.91 2.449 0.236 77 84 1.50
25 1.20 1.539 0.242 101 107 2.35
35 0.868 1.113 0.234 125 129 3.29
50 0.641 0.822 0.232 155 157 4.70
70 0.443 0.568 0.229 195 193 6.58
95 0.320 0.411 0.224 240 231 8.93
120 0.253 0.325 0.223 279 263 11.28
150 0.206 0.265 0.225 319 294 14.10
185 0.164 0.211 0.225 370 335 17.39
240 0.125 0.162 0.223 439 388 22.56
300 0.100 0.130 0.222 506 439 28.20

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information