NA2XSY 2 x (10-300) mm² 0.6/1 kV

Al / XLPE / CTS / PVC
(Aluminium Conductor, XLPE Insulated, Copper Tape Screen, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For power plants and switchgear as well as
for installation of sub-station; for installation
indoors in confinned spaces and cable channels
because of small bending radius. As burried
cable, because of its light weight prefered in
where installation is difficult.


Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated

Note :
Conductor Shape
10 - 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
10 - 185 sqmm supplied in wooden drum @ 1000 m
240 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
10 16.9 352
16 19.4 464
25 22.0 589
35 24.5 733
50 27.5 863
70 31.5 1,124
95 35.5 1,465
120 39.0 1,770
150 42.0 2,079
185 48.0 2,635
240 53.0 3,255
300 58.5 3,985

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
10 3.08 3.949 0.248 68 76 0.94
16 1.91 2.449 0.236 92 101 1.50
25 1.20 1.539 0.242 120 129 2.35
35 0.868 1.113 0.234 148 156 3.29
50 0.641 0.822 0.232 180 185 4.70
70 0.443 0.568 0.229 228 228 6.58
95 0.320 0.411 0.224 279 272 8.93
120 0.253 0.325 0.223 324 310 11.28
150 0.206 0.265 0.225 367 346 14.10
185 0.164 0.211 0.225 427 393 17.39
240 0.125 0.162 0.223 504 455 22.56
300 0.100 0.130 0.222 577 513 28.20

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information