NA2XSY 3 x (10-300) mm² 0.6/1 kV

Al / XLPE / CTS / PVC
(Aluminium Conductor, XLPE Insulated, Copper Tape Screen, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For power plants and switchgear as well as
for installation of sub-station; for installation
indoors in confinned spaces and cable channels
because of small bending radius. As burried
cable, because of its light weight prefered in
where installation is difficult.

Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated

Note :
Conductor Shape
10 - 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor

Standard Packing
10 - 185 sqmm supplied in wooden drum @ 1000 m
240 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
10 17.8 390
16 21.0 518
25 23.0 667
35 26.0 835
50 28.0 856
70 32.0 1,155
95 35.5 1,454
120 39.0 1,769
150 43.5 2,149
185 48.5 2,616
240 54.0 3,317
300 59.0 4,005

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
10 3.08 3.949 0.248 58 64 0.94
16 1.91 2.449 0.236 78 85 1.50
25 1.20 1.539 0.242 102 108 2.35
35 0.868 1.113 0.234 126 131 3.29
50 0.641 0.822 0.232 156 159 4.70
70 0.443 0.568 0.229 197 194 6.58
95 0.320 0.411 0.224 242 233 8.93
120 0.253 0.325 0.223 281 265 11.28
150 0.206 0.265 0.225 321 296 14.10
185 0.164 0.211 0.225 373 337 17.39
240 0.125 0.162 0.223 442 390 22.56
300 0.100 0.130 0.222 509 440 28.20

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information