NA2XSY 4 x (10-300) mm² 0.6/1 kV

Al / XLPE / CTS / PVC
(Aluminium Conductor, XLPE Insulated, Copper Tape Screen, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For power plants and switchgear as well as
for installation of sub-station; for installation
indoors in confinned spaces and cable channels
because of small bending radius. As burried
cable, because of its light weight prefered in
where installation is difficult.


Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated

Note :
Conductor Shape
10 - 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor

Standard Packing
10 - 120 sqmm supplied in wooden drum @ 1000 m
150 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
10
19.3 456
16 22.5 612
25 25.0 797
35 28.0 1,003
50 32.0 1,090
70 36.5 1,464
95 40.5 1,875
120 45.5 2,312
150 51.5 2,814
185 55.5 3,382
240 62.0 4,288
300 68.0 5,180

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
10 3.08 3.949 0.248 63 70 0.94
16 1.91 2.449 0.236 86 91 1.50
25 1.20 1.539 0.242 113 118 2.35
35 0.868 1.113 0.234 140 141 3.29
50 0.641 0.822 0.232 165 163 4.70
70 0.443 0.568 0.229 208 199 6.58
95 0.320 0.411 0.224 255 238 8.93
120 0.253 0.325 0.223 297 271 11.28
150 0.206 0.265 0.225 345 306 14.10
185 0.164 0.211 0.225 396 345 17.39
240 0.125 0.162 0.223 469 400 22.56
300 0.100 0.130 0.222 540 452 28.20

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information