NA2XBY 2 x (10-300) mm² 0.6/1 kV

Al / XLPE / STA / PVC
(Aluminium Conductor, XLPE Insulated, Galvanized Steel Tape Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For installation indoors, cable channels and in
ground, for industry installations, switchgear,
and power station, if there is a risk that low
mechanical damage may occur.


Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen

Note :
Conductor Shape
10 - 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
10 - 150 sqmm supplied in wooden drum @ 1000 m
185 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
10
17.4 406
16 19.9 527
25 22.5 660
35 25.0 813
50 28.0 954
70 32.0 1,244
95 36.0 1,585
120 40.5 2,278
150 44.0 2,648
185 50.0 3,288
240 55.0 3,973
300
60.5 4,751

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
10 3.08 3.949 0.248 68 77 0.94
16 1.91 2.449 0.236 92 101 1.50
25 1.20 1.539 0.242 121 129 2.35
35 0.868 1.113 0.234 149 156 3.29
50 0.641 0.822 0.232 181 185 4.70
70 0.443 0.568 0.229 229 228 6.58
95 0.320 0.411 0.224 280 272 8.93
120 0.253 0.325 0.223 329 312 11.28
150 0.206 0.265 0.225 371 347 14.10
185 0.164 0.211 0.225 431 394 17.39
240 0.125 0.162 0.223 508 456 22.56
300 0.100 0.130 0.222 582 514 28.20

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information