NA2XBY 3 x (10-300) mm² 0.6/1 kV

Al / XLPE / STA / PVC
(Aluminium Conductor, XLPE Insulated, Galvanized Steel Tape Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For installation indoors, cable channels and in
ground, for industry installations, switchgear,
and power station, if there is a risk that low
mechanical damage may occur.


Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen

Note :
Conductor Shape
10 - 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor

Standard Packing
10 - 150 sqmm supplied in wooden drum @ 1000 m
185 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
10
18.2 448
16 21.0 585
25 23.5 743
35 26.0 920
50 28.5 948
70 32.5 1,262
95 36.0 1,589
120 41.0 2,272
150 45.5 2,732
185 50.0 3,262
240 56.0 4,040
300 61.0 4,793

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
10 3.08 3.949 0.248 58 64 0.94
16 1.91 2.449 0.236 78 85 1.50
25 1.20 1.539 0.242 103 109 2.35
35 0.868 1.113 0.234 127 131 3.29
50 0.641 0.822 0.232 157 159 4.70
70 0.443 0.568 0.229 198 194 6.58
95 0.320 0.411 0.224 242 232 8.93
120 0.253 0.325 0.223 285 266 11.28
150 0.206 0.265 0.225 325 297 14.10
185 0.164 0.211 0.225 377 337 17.39
240 0.125 0.162 0.223 446 391 22.56
300 0.100 0.130 0.222 512 441 28.20

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information