NA2XBY 4 x (10-300) mm² 0.6/1 kV

Al / XLPE / STA / PVC
(Aluminium Conductor, XLPE Insulated, Galvanized Steel Tape Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For installation indoors, cable channels and in
ground, for industry installations, switchgear,
and power station, if there is a risk that low
mechanical damage may occur.


Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen

Note :
Conductor Shape
10 - 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor

Standard Packing
10 - 120 sqmm supplied in wooden drum @ 1000 m
150 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
10 19.7 519
16 23.0 685
25 25.5 880
35 28.5 1,097
50 32.5 1,196
70 37.0 1,586
95 42.5 2,399
120 47.5 2,919
150 53.5 3,482
185 57.5 4,125
240 64.0 5,122
300 69.5 6,088

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
10 3.08 3.949 0.248 64 70 0.94
16 1.91 2.449 0.236 86 91 1.50
25 1.20 1.539 0.242 114 118 2.35
35 0.868 1.113 0.234 141 142 3.29
50 0.641 0.822 0.232 166 163 4.70
70 0.443 0.568 0.229 209 199 6.58
95 0.320 0.411 0.224 259 239 8.93
120 0.253 0.325 0.223 300 272 11.28
150 0.206 0.265 0.225 349 307 14.10
185 0.164 0.211 0.225 399 346 17.39
240 0.125 0.162 0.223 473 401 22.56
300 0.100 0.130 0.222 543 453 28.20

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information