NA2XBY 5 x (10-50) mm² 0.6/1 kV

Al / XLPE / STA / PVC
(Aluminium Conductor, XLPE Insulated, Galvanized Steel Tape Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For installation indoors, cable channels and in
ground, for industry installations, switchgear,
and power station, if there is a risk that low
mechanical damage may occur.


Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen

Note :
Conductor Shape
10 - 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 50 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
10 - 50 sqmm supplied in wooden drum @ 1000 m
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
10 21.5 602
16 25.0 802
25 28.0 1,038
35 31.5 1,315
50 36.0 1,632

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
10 3.08 3.949 0.248 66 71 0.94
16 1.91 2.449 0.236 89 93 1.50
25 1.20 1.539 0.242 119 120 2.35
35 0.868 1.113 0.234 146 144 3.29
50 0.641 0.822 0.232 179 170 4.70

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information