NA2XRY 3 x (10-300) mm² 0.6/1 kV

Al / XLPE / SWA / PVC
(Aluminium Conductor, XLPE Insulated, Galvanized Steel Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For installation in the ground, indoors, cable
trunking and outdoors if increased mechanical
protection is required or where high-pulling
stresses may occur during installation or
operation.


Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
10 - 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor

Standard Packing
10 - 150 sqmm supplied in wooden drum @ 1000 m
185 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
10
20.5 712
16
23.5 893
25
26.5 1,232
35
29.0 1,458
50
31.5 1,553
70
36.5 2,182
95
40.0 2,597
120
43.5 2,994
150
49.5 3,959
185
54.0 4,583
240
60.0 5,522
300
65.0 6,408

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
10
3.08 3.949 0.248 60 65 0.94
16
1.91 2.449 0.236 81 86 1.50
25
1.20 1.539 0.242 106 110 2.35
35
0.868 1.113 0.234 131 133 3.29
50
0.641 0.822 0.232 162 161 4.70
70
0.443 0.568 0.229 205 197 6.58
95
0.320 0.411 0.224 250 235 8.93
120
0.253 0.325 0.223 290 267 11.28
150
0.206 0.265 0.225 332 299 14.10
185
0.164 0.211 0.225 384 338 17.39
240
0.125 0.162 0.223 451 390 22.56
300
0.100 0.130 0.222 516 438 28.20

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information