NA2XRY 4 x (10-300) mm² 0.6/1 kV

Al / XLPE / SWA / PVC
(Aluminium Conductor, XLPE Insulated, Galvanized Steel Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For installation in the ground, indoors, cable
trunking and outdoors if increased mechanical
protection is required or where high-pulling
stresses may occur during installation or
operation.


Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
10 - 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor

Standard Packing
10 - 95 sqmm supplied in wooden drum @ 1000 m
120 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
10
22.0 805
16
26.0 1,161
25
28.5 1,405
35
31.5 1,700
50
35.5 1,880
70
41.0 2,631
95
45.0 3,148
120
51.5 4,159
150
57.5 4,913
185
61.5 5,664
240
68.0 6,807
300
73.5 7,937

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
10
3.08 3.949 0.248 66 71 0.94
16
1.91 2.449 0.236 90 93 1.50
25
1.20 1.539 0.242 119 120 2.35
35
0.868 1.113 0.234 146 143 3.29
50
0.641 0.822 0.232 171 165 4.70
70
0.443 0.568 0.229 215 201 6.58
95
0.320 0.411 0.224 263 240 8.93
120
0.253 0.325 0.223 307 273 11.28
150
0.206 0.265 0.225 355 308 14.10
185
0.164 0.211 0.225 405 346 17.39
240
0.125 0.162 0.223 476 399 22.56
300
0.100 0.130 0.222 544 448 28.20

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information