NA2XKBY 3 x (10-300) mm² 0.6/1 kV

Al / XLPE / LS / PVC / DSTA / PVC
(Aluminium Conductor, XLPE Insulated, Lead Sheathed, Double Galvanized Steel Tape Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For indoors, outdoors, in ground and in duct.
Mainly on chemical industries, refineries, petrol
stations and any other locations where there
is a risk that solvent, fuel and other chemicals
may penetrate and low mechanical damage may
occur.


Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
10 - 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor

Standard Packing
10 - 95 sqmm supplied in wooden drum @ 1000 m
120 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
10 22.5 1,207
16 25.5 1,465
25 27.5 1,729
35 30.5 2,114
50 33.0 2,264
70 39.0 3,261
95 43.0 3,934
120 46.5 4,593
150 51.5 5,469
185 57.0 6,496
240 63.5 8,045
300
68.5 9,377

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
10 3.08 3.949 0.248 60 64 0.94
16 1.91 2.449 0.236 81 84 1.50
25 1.20 1.539 0.242 105 108 2.35
35 0.868 1.113 0.234 129 130 3.29
50 0.641 0.822 0.232 160 157 4.70
70 0.443 0.568 0.229 203 193 6.58
95 0.320 0.411 0.224 247 231 8.93
120 0.253 0.325 0.223 287 263 11.28
150 0.206 0.265 0.225 326 294 14.10
185 0.164 0.211 0.225 376 333 17.39
240 0.125 0.162 0.223 443 384 22.56
300 0.100 0.130 0.222 507 433 28.20

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information