NA2XKBY 4 x (10-300) mm² 0.6/1 kV

Al / XLPE / LS / PVC / DSTA / PVC
(Aluminium Conductor, XLPE Insulated, Lead Sheathed, Double Galvanized Steel Tape Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For indoors, outdoors, in ground and in duct.
Mainly on chemical industries, refineries, petrol
stations and any other locations where there
is a risk that solvent, fuel and other chemicals
may penetrate and low mechanical damage may
occur.


Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
10 - 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor

Standard Packing
10 - 50 sqmm supplied in wooden drum @ 1000 m
70 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
10 24.0 1,344
16 27.0 1,646
25 30.0 2,044
35 33.0 2,421
50 37.5 2,827
70 44.0 4,009
95 48.5 4,812
120 53.5 5,762
150 60.0 6,932
185 65.0 8,240
240 72.0 10,172
300 78.0 11,838

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
10 3.08 3.949 0.248 66 69 0.94
16 1.91 2.449 0.236 89 91 1.50
25 1.20 1.539 0.242 117 117 2.35
35 0.868 1.113 0.234 143 140 3.29
50 0.641 0.822 0.232 168 161 4.70
70 0.443 0.568 0.229 212 197 6.58
95 0.320 0.411 0.224 260 237 8.93
120 0.253 0.325 0.223 301 269 11.28
150 0.206 0.265 0.225 347 303 14.10
185 0.164 0.211 0.225 397 341 17.39
240 0.125 0.162 0.223 467 394 22.56
300 0.100 0.130 0.222 534 443 28.20

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information