NA2XKFGbY 4 x (10-300) mm² 0.6/1 kV

Al / XLPE / LS / PVC / SFWA / PVC
(Aluminium Conductor, XLPE Insulated, Lead Sheathed, Galvanized Steel Flat Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For indoors, outdoors, in ground and in duct.
Mainly on chemical industries, refineries, petrol
stations and any other locations where that is a
risk that solvent, fuel and other chemicals may
penetrate and high pulling stresses may occur
during installation and operation.


Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
10 - 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor

Standard Packing
10 - 50 sqmm supplied in wooden drum @ 1000 m
70 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
10 25.5 1,694
16 28.5 2,042
25 31.5 2,502
35 35.0 2,928
50 39.0 3,392
70 44.5 4,242
95 48.5 5,076
120 54.0 6,072
150 60.5 7,269
185 65.0 8,608
240 72.5 10,592
300
78.5 12,273

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
10 3.08 3.949 0.248 67 70 0.94
16 1.91 2.449 0.236 90 91 1.50
25 1.20 1.539 0.242 119 117 2.35
35 0.868 1.113 0.234 145 140 3.29
50 0.641 0.822 0.232 171 162 4.70
70 0.443 0.568 0.229 213 197 6.58
95 0.320 0.411 0.224 260 237 8.93
120 0.253 0.325 0.223 301 268 11.28
150 0.206 0.265 0.225 348 303 14.10
185 0.164 0.211 0.225 397 341 17.39
240 0.125 0.162 0.223 467 393 22.56
300 0.100 0.130 0.222 533 442 28.20

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information