NA2XKRY 3 x (10-300) mm² 0.6/1 kV

Al / XLPE / LS / PVC / SWA / PVC
(Aluminium Conductor, XLPE Insulated, Lead Sheathed, Galvanized Steel Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For indoors, outdoors, in ground and in duct.
Mainly on chemical industries, refineries, petrol
stations and any other locations where that is a
risk that solvent, fuel and other chemicals may
penetrate and high pulling stresses may occur
during installation and operation.


Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
10 - 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor

Standard Packing
10 - 70 sqmm supplied in wooden drum @ 1000 m
95 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
10 25.5 1,669
16 28.0 1,992
25 30.5 2,307
35 33.5 2,771
50 37.0 3,183
70 42.0 3,954
95 45.5 4,681
120 50.5 5,842
150 56.0 6,872
185 61.0 8,003
240 67.5 9,743
300
72.5 11,202

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
10 3.08 3.949 0.248 62 65 0.94
16 1.91 2.449 0.236 83 85 1.50
25 1.20 1.539 0.242 108 109 2.35
35 0.868 1.113 0.234 133 131 3.29
50 0.641 0.822 0.232 165 159 4.70
70 0.443 0.568 0.229 206 194 6.58
95 0.320 0.411 0.224 252 233 8.93
120 0.253 0.325 0.223 294 266 11.28
150 0.206 0.265 0.225 333 296 14.10
185 0.164 0.211 0.225 384 336 17.39
240 0.125 0.162 0.223 452 388 22.56
300 0.100 0.130 0.222 517 438 28.20

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information