NA2XKRY 4 x (10-300) mm² 0.6/1 kV

Al / XLPE / LS / PVC / SWA / PVC
(Aluminium Conductor, XLPE Insulated, Lead Sheathed, Galvanized Steel Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For indoors, outdoors, in ground and in duct.
Mainly on chemical industries, refineries, petrol
stations and any other locations where that is a
risk that solvent, fuel and other chemicals may
penetrate and high pulling stresses may occur
during installation and operation.


Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
10 - 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor

Standard Packing
10 - 50 sqmm supplied in wooden drum @ 1000 m
70 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
10 27.0 1,846
16 30.0 2,211
25 33.0 2,688
35 37.0 3,362
50 41.5 3,878
70 46.5 4,766
95 52.5 6,117
120 57.5 7,219
150 64.0 8,549
185 69.0 9,955
240 76.0 12,104
300
83.5 14,803

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
10 3.08 3.949 0.248 68 70 0.94
16 1.91 2.449 0.236 92 92 1.50
25 1.20 1.539 0.242 121 118 2.35
35 0.868 1.113 0.234 149 142 3.29
50 0.641 0.822 0.232 174 163 4.70
70 0.443 0.568 0.229 216 199 6.58
95 0.320 0.411 0.224 267 239 8.93
120 0.253 0.325 0.223 308 271 11.28
150 0.206 0.265 0.225 355 306 14.10
185 0.164 0.211 0.225 405 344 17.39
240 0.125 0.162 0.223 477 398 22.56
300 0.100 0.130 0.222 547 449 28.20

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information