NA2XKRY 5 x (10-50) mm² 0.6/1 kV

Al / XLPE / LS / PVC / SWA / PVC
(Aluminium Conductor, XLPE Insulated, Lead Sheathed, Galvanized Steel Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For indoors, outdoors, in ground and in duct.
Mainly on chemical industries, refineries, petrol
stations and any other locations where that is a
risk that solvent, fuel and other chemicals may
penetrate and high pulling stresses may occur
during installation and operation.


Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
10 - 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 50 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
10 - 35 sqmm supplied in wooden drum @ 1000 m
50 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
10 28.5 2,025
16 32.0 2,453
25 35.5 3,026
35 40.5 3,922
50 45.0 4,800

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
10 3.08 3.949 0.248 71 72 0.94
16 1.91 2.449 0.236 95 93 1.50
25 1.20 1.539 0.242 124 120 2.35
35 0.868 1.113 0.234 153 144 3.29
50 0.641 0.822 0.232 185 169 4.70

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information