NA2XKY 2 x (10-300) mm² 0.6/1 kV

Al / XLPE / LS / PVC
(Aluminium Conductor, XLPE Insulated, Lead Sheathed, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For indoors, outdoors, in ground and in duct.
Mainly on chemical industries, refineries, petrol
stations and any other locations where there is
a risk that solvent, fuel and other chemicals may
penetrate and mechanical damage is not likely
to occur.


Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated


Note :
Conductor Shape
10 - 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
10 - 120 sqmm supplied in wooden drum @ 1000 m
150 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
10 19.7 954
16
22.5 1,163
25
24.5 1,374
35
27.0 1,616
50 30.0 1,995
70
34.5 2,571
95
38.5 3,233
120
42.5 3,865
150
46.0 4,500
185
52.0 5,611
240
57.5 6,916
300
63.0 8,255

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
10 3.08 3.949 0.248 70 77 0.94
16 1.91 2.449 0.236 95 101 1.50
25 1.20 1.539 0.242 123 129 2.35
35 0.868 1.113 0.234 151 156 3.29
50 0.641 0.822 0.232 183 185 4.70
70 0.443 0.568 0.229 232 228 6.58
95 0.320 0.411 0.224 283 272 8.93
120 0.253 0.325 0.223 329 310 11.28
150 0.206 0.265 0.225 372 346 14.10
185 0.164 0.211 0.225 433 394 17.39
240 0.125 0.162 0.223 510 456 22.56
300 0.100 0.130 0.222 584 514 28.20

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information