NA2XKY 3 x (10-300) mm² 0.6/1 kV

Al / XLPE / LS / PVC
(Aluminium Conductor, XLPE Insulated, Lead Sheathed, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For indoors, outdoors, in ground and in duct.
Mainly on chemical industries, refineries, petrol
stations and any other locations where there is
a risk that solvent, fuel and other chemicals may
penetrate and mechanical damage is not likely
to occur.


Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated


Note :
Conductor Shape
10 - 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor

Standard Packing
10 - 120 sqmm supplied in wooden drum @ 1000 m
150 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
10 21.0 1,026
16 23.5 1,260
25 26.0 1,502
35 28.5 1,861
50 31.0 1,978
70 35.5 2,559
95 39.0 3,123
120 43.0 3,729
150 47.5 4,485
185 52.5 5,385
240 59.0 6,776
300 64.0 7,940

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
10 3.08 3.949 0.248 60 65 0.94
16 1.91 2.449 0.236 80 85 1.50
25 1.20 1.539 0.242 105 109 2.35
35 0.868 1.113 0.234 129 131 3.29
50 0.641 0.822 0.232 160 159 4.70
70 0.443 0.568 0.229 201 195 6.58
95 0.320 0.411 0.224 247 233 8.93
120 0.253 0.325 0.223 286 266 11.28
150 0.206 0.265 0.225 327 297 14.10
185 0.164 0.211 0.225 379 337 17.39
240 0.125 0.162 0.223 449 391 22.56
300 0.100 0.130 0.222 517 442 28.20

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information