NA2XKY 4 x (10-300) mm² 0.6/1 kV

Al / XLPE / LS / PVC
(Aluminium Conductor, XLPE Insulated, Lead Sheathed, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For indoors, outdoors, in ground and in duct.
Mainly on chemical industries, refineries, petrol
stations and any other locations where there is
a risk that solvent, fuel and other chemicals may
penetrate and mechanical damage is not likely
to occur.


Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated


Note :
Conductor Shape
10 - 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor

Standard Packing
10 - 95 sqmm supplied in wooden drum @ 1000 m
120 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
10 22.5 1,150
16
25.5 1,424
25
28.0 1,797
35
31.0 2,131
50 35.5 2,484
70
40.0 3,178
95
44.5 3,916
120
49.5 4,743
150
56.0 5,753
185
60.0 6,913
240
67.5 8,688
300
73.5 10,193

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
10 3.08 3.949 0.248 65 70 0.94
16 1.91 2.449 0.236 88 92 1.50
25 1.20 1.539 0.242 117 118 2.35
35 0.868 1.113 0.234 144 142 3.29
50 0.641 0.822 0.232 169 163 4.70
70 0.443 0.568 0.229 212 199 6.58
95 0.320 0.411 0.224 260 239 8.93
120 0.253 0.325 0.223 302 272 11.28
150 0.206 0.265 0.225 350 307 14.10
185 0.164 0.211 0.225 402 347 17.39
240 0.125 0.162 0.223 476 401 22.56
300 0.100 0.130 0.222 546 453 28.20

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information