N2XY 5 x (1.5-50) mm2 0.6/1 kV

Cu / XLPE / PVC
(Copper Conductor, XLPE Insulated, PVC Sheathed)
Standard Specification : SNI IEC 60502-1 : 2009

Application

Power cable : Indoors, cable trunking, outdoors
and burried in the ground, for power stations,
industry and switchgear as well as for urban
supply networks, if mechanical damage is
unlikely.

Special Features on Request :
• Tinned Coated Copper Conductor
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated


Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 50 sqmm supplied in compacted circular stranded (cm) conductor shape

Tinned Coated Copper Conductor
Electrical properties for tinned coated copper conductor will be submitted upon request

Standard Packing
1.5 - 50 sqmm supplied in wooden drum @ 1000 m
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
1.5 14.2 269
2.5 15.5 345
4 17.0 453
6 18.5 579
10 21.5 838
16 24.0 1,174
25 28.5 1,728
35 31.5 2,273
50 36.0 2,917

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
1.5 12.1 15.429 0.315 27 32 0.21
2.5 7.41 9.449 0.293 36 42 0.36
4 4.61 5.878 0.275 48 54 0.57
6 3.08 3.927 0.263 61 68 0.86
10 1.83 2.334 0.248 84 91 1.43
16 1.15 1.467 0.238 112 118 2.29
25 0.727 0.927 0.240 152 153 3.58
35 0.524 0.669 0.233 187 184 5.01
50 0.387 0.494 0.232 227 217 7.15

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information