N2XY 2 x (1.5-300) mm2 0.6/1 kV

Cu / XLPE / PVC
(Copper Conductor, XLPE Insulated, PVC Sheathed)
Standard Specification : SNI IEC 60502-1 : 2009

Application

Power cable : Indoors, cable trunking, outdoors
and burried in the ground, for power stations,
industry and switchgear as well as for urban
supply networks, if mechanical damage is
unlikely.

Special Features on Request :
• Tinned Coated Copper Conductor
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated


Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Tinned Coated Copper Conductor
Electrical properties for tinned coated copper conductor will be submitted upon request

Standard Packing
1.5 - 150 sqmm supplied in wooden drum @ 1000 m
185 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
1.5 12.0 182
2.5 13.0 223
4 14.1 279
6 15.2 344
10 17.2 474
16 19.2 639
25 22.5 912
35 25.0 1,173
50 27.5 1,411
70 31.5 1,929
95 35.5 2,589
120 39.0 3,182
150 43.5 3,894
185 48.0 4,847
240 54.0 6,217
300 59.5 7,697

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
1.5 12.1 15.429 0.315 29 34 0.21
2.5 7.41 9.449 0.293 38 44 0.36
4 4.61 5.878 0.275 50 58 0.57
6 3.08 3.927 0.263 64 73 0.86
10 1.83 2.334 0.248 88 98 1.43
16 1.15 1.467 0.238 116 128 2.29
25 0.727 0.927 0.240 154 165 3.58
35 0.524 0.669 0.233 190 199 5.01
50 0.387 0.494 0.232 230 236 7.15
70 0.268 0.342 0.229 292 292 10.01
95 0.193 0.247 0.224 356 348 13.59
120 0.153 0.196 0.223 414 397 17.16
150 0.124 0.160 0.224 474 445 21.45
185 0.0991 0.128 0.225 544 502 26.46
240 0.0754 0.099 0.223 644 582 34.32
300 0.0601 0.080 0.221 737 654 42.90

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information