NYCY 3 x (1.5-300) mm2 0.6/1 kV

Cu / PVC / CWS / PVC
(Copper Conductor, PVC Insulated, Copper Wire Screen, PVC Sheathed)
Standard Specification : SNI IEC 60502-1 : 2009

Application

For installation in the ground, indoors, cable
trunking and outdoors if subsequent mechanical
damage is likely. For urban networks, household
feeders and street lighting.

Special Features on Request :
• Tinned Coated Copper Conductor
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Heat Resistance
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor

Tinned Coated Copper Conductor
Electrical properties for tinned coated copper conductor will be submitted upon request

Standard Packing
1.5 - 95 sqmm supplied in wooden drum @ 1000 m
120 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
1.5/1.5 13.9 242
2.5/2.5 14.9 298
4/4 17.0 405
6/6 18.2 509
10/10 20.5 719
16/16 23.0 1,001
25/16 26.5 1,365
35/16 29.0 1,716
50/25 32.5 2,089
70/35 35.5 2,856
95/50 40.5 3,865
120/70 44.0 4,787
150/70 48.5 5,742
185/95 53.5 7,177
240/120 60.0 9,295
300/150 66.0 11,468

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 70°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
1.5/1.5 12.1 14.478 0.328 20 24 0.17
2.5/2.5 7.41 8.866 0.304 27 31 0.29
4/4 4.61 5.516 0.303 35 41 0.46
6/6 3.08 3.685 0.288 45 51 0.69
10/10 1.83 2.190 0.269 61 69 1.15
16/16 1.15 1.376 0.255 82 90 1.84
25/16 0.727 0.870 0.255 108 115 2.88
35/16 0.524 0.627 0.246 132 139 4.03
50/25 0.387 0.464 0.247 167 171 5.75
70/35 0.268 0.321 0.238 208 208 8.05
95/50 0.193 0.232 0.238 255 250 10.93
120/70 0.153 0.184 0.233 296 284 13.80
150/70 0.124 0.150 0.233 337 317 17.25
185/95 0.0991 0.121 0.233 386 356 21.28
240/120 0.0754 0.093 0.232 454 409 27.60
300/150 0.0601 0.075 0.231 516 456 34.50

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information