NYR(AL)Y 1 x (10-500) mm² 0.6/1 kV

Cu / PVC / AWA / PVC
(Copper Conductor, PVC Insulated, Aluminium Wire Armor, PVC Sheathed)
Standard Specification : SNI IEC 60502-1 : 2009

Application

For installation in the ground, indoors, cable
trunking and outdoors if increased mechanical
protection is required or where high-pulling
stresses may occur during installation or
operation.

Special Features on Request :
• Tinned Coated Copper Conductor
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Heat Resistance
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 500 sqmm supplied in non compacted circular stranded (rm) or compacted circular stranded (cm) conductor shape

Tinned Coated Copper Conductor
Electrical properties for tinned coated copper conductor will be submitted upon request

Standard Packing
10 - 300 sqmm supplied in wooden drum @ 1000 m
400 - 500 sqmm supplied wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
10 14.4 326
16
15.4 402
25
17.2 541
35
18.3 658
50
20.5 841
70
22.5 1,070
95
24.5 1,365
120
26.5 1,662
150
28.5 1,967
185
31.0 2,406
240
34.0 3,071
300
38.0 3,781
400
42.0 4,764
500 46.5 5,968

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 70°C
Trefoil formation
Flat formation
in air in ground in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) (mH/km) Max. (A) Max. (A) Max. (A) Max. (A) Max. (kA)
10 1.83 2.190 0.442 0.489 73 77 75 79 1.15
16
1.15 1.376 0.412 0.458 96 99 98 102 1.84
25
0.727 0.870 0.386 0.432 127 128 130 131 2.88
35
0.524 0.627 0.367 0.414 154 153 158 157 4.03
50
0.387 0.463 0.351 0.397 187 181 192 186 5.75
70
0.268 0.321 0.333 0.379 234 222 240 227 8.05
95
0.193 0.232 0.322 0.368 286 264 292 269 10.93
120
0.153 0.184 0.315 0.361 331 299 338 304 13.80
150
0.124 0.150 0.309 0.355 376 334 383 338 17.25
185
0.0991 0.120 0.302 0.348 431 375 438 378 21.28
240
0.0754 0.092 0.294 0.340 507 429 511 430 27.60
300
0.0601 0.075 0.293 0.340 573 472 573 468 34.50
400
0.0470 0.060 0.290 0.337 650 522 644 513 41.20
500 0.0366 0.048 0.284 0.330 732 573 719 557 51.50

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information