NYFGbY 5 x (1.5-50) mm² 0.6/1 kV

Cu / PVC / SFWA / PVC
(Copper Conductor, PVC Insulated, Galvanized Steel Flat Wire Armor, PVC Sheathed)
Standard Specification : SNI IEC 60502-1 : 2009

Application

For installation in the ground, indoors, cable trunking and outdoors if increased mechanical protection is required or where high-pulling stresses may occur during installation or operation.

Special Features on Request :
• Tinned Coated Copper Conductor
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Heat Resistance
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 50 sqmm supplied in compacted circular stranded (cm) conductor shape

Tinned Coated Copper Conductor
Electrical properties for tinned coated copper conductor will be submitted upon request

Standard Packing
1.5 - 50 sqmm supplied in wooden drum @ 1000 m
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
1.5 17.8 642
2.5 17.9 682
4 20.5 891
6 22 1056
10 24.5 1391
16 27.5 1778
25 32 2463
35 35 3106
50 40 3904

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 70°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
1.5 12.1 14.478 0.340 24 28 0.17
2.5 7.41 8.866 0.304 32 37 0.29
4 4.61 5.516 0.303 43 48 0.46
6 3.08 3.685 0.288 54 60 0.69
10 1.83 2.190 0.269 74 80 1.15
16 1.15 1.376 0.255 97 103 1.84
25 0.727 0.870 0.255 130 133 2.88
35 0.524 0.627 0.246 160 159 4.03
50 0.387 0.464 0.247 194 188 5.75

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information