NYBY 5 x (1.5-50) mm² 0.6/1 kV

Cu / PVC / STA / PVC
(Copper Conductor, PVC Insulated, Galvanized Steel Tape Armor, PVC Sheathed)
Standard Specification : SNI IEC 60502-1 : 2009

Application

For installation indoors, cable channels and in
ground, for industry installations, switchgear,
and power station, if there is a risk that low
mechanical damage may occur.

Special Features on Request :
• Tinned Coated Copper Conductor
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Heat Resistance
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen

Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 50 sqmm supplied in compacted circular stranded (cm) conductor shape

Tinned Coated Copper Conductor
Electrical properties for tinned coated copper conductor will be submitted upon request

Standard Packing
1.5 - 50 sqmm supplied in wooden drum @ 1000 m
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
1.5 15.0 357
2.5 16.3 443
4 18.9 612
6 20.5 754
10 23.5 1,041
16 26.0 1,406
25 30.0 2,006
35 33.5 2,599
50 38.5 3,342

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 70°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
1.5 12.1 14.478 0.328 23 28 0.17
2.5 7.41 8.866 0.304 31 36 0.29
4 4.61 5.516 0.303 42 48 0.46
6 3.08 3.685 0.288 53 59 0.69
10 1.83 2.190 0.269 72 79 1.15
16 1.15 1.376 0.255 95 102 1.84
25 0.727 0.870 0.255 128 132 2.88
35 0.524 0.627 0.246 157 158 4.03
50 0.387 0.464 0.247 191 186 5.75

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information