N2XFGbY 2 x (1.5-300) mm² 0.6/1 kV

Cu / XLPE / SFWA / PVC
(Copper Conductor, XLPE Insulated, Galvanized Steel Flat Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For installation in the ground, indoors, cable trunking and outdoors if increased mechanical protection is required or where high-pulling stresses may occur during installation or operation.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
1.5 - 120 sqmm supplied in wooden drum @ 1000 m
150 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
1.5 17.9 603
2.5 17.9 621
4 17.9 638
6 17.9 669
10 18.8 789
16 21.0 983
25 24.0 1,311
35 26.5 1,626
50 29.5 1,950
70 33.5 2,548
95 37.0 3,280
120 41.0 3,937
150 45.5 4,760
185 50.0 5,803
240 55.5 7,270
300 61.0 8,862

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
1.5 12.1 15.429 0.340 30 33 0.21
2.5 7.41 9.449 0.315 40 44 0.36
4 4.61 5.878 0.285 53 58 0.57
6 3.08 3.927 0.263 66 74 0.86
10 1.83 2.334 0.248 91 101 1.43
16 1.15 1.467 0.238 121 131 2.29
25 0.727 0.927 0.240 160 168 3.58
35 0.524 0.669 0.233 196 203 5.01
50 0.387 0.494 0.232 237 240 7.15
70 0.268 0.342 0.229 299 295 10.01
95 0.193 0.247 0.224 365 353 13.59
120 0.153 0.196 0.223 424 401 17.16
150 0.124 0.160 0.224 483 449 21.45
185 0.0991 0.128 0.225 553 505 26.46
240 0.0754 0.099 0.223 653 585 34.32
300 0.0601 0.080 0.221 746 658 42.90

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information