NYKY 1 x (16-800) mm² 0.6/1 kV

Cu / PVC / LS / PVC
(Copper Conductor, PVC Insulated, Lead Sheathed, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For indoors, outdoors, in ground and in duct.
Mainly on chemical industries, refineries, petrol
stations and any other locations where there is
a risk that solvent, fuel and other chemicals may
penetrate and mechanical damage is not likely
to occur.


Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Heat Resistance
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated


Note :
Conductor Shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 800 sqmm supplied in non compacted circular stranded (rm) or compacted circular stranded (cm) conductor shape

Standard Packing
16 - 185 sqmm supplied in wooden drum @ 1000 m
240 - 800 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
16
17.7 956
25
17.7 1,026
35
17.7 1,085
50
19.7 1,340
70
21.5 1,629
95
24.5 2,079
120
26.0 2,408
150
28.0 2,783
185
31.0 3,418
240
34.5 4,310
300
37.5 5,173
400
41.5 6,431
500 46.0 7,815
630 50.5 9,754
800 55.5 11,974

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 70°C
Trefoil formation
Flat formation
in air in ground in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) (mH/km) Max. (A) Max. (A) Max. (A) Max. (A) Max. (kA)
16
1.15 1.376 0.439 0.486 97 98 99 100 1.84
25
0.727 0.870 0.391 0.437 126 127 129 130 2.88
35
0.524 0.627 0.358 0.405 152 153 157 157 4.03
50
0.387 0.463 0.345 0.391 186 181 191 186 5.75
70
0.268 0.321 0.327 0.374 233 222 239 228 8.05
95
0.193 0.232 0.320 0.366 287 266 295 273 10.93
120
0.153 0.184 0.311 0.357 332 302 342 310 13.80
150
0.124 0.150 0.305 0.352 379 338 389 347 17.25
185
0.0991 0.120 0.301 0.347 438 382 450 391 21.28
240
0.0754 0.092 0.295 0.341 521 442 535 452 27.60
300
0.0601 0.075 0.291 0.337 599 497 613 507 34.50
400
0.0470 0.060 0.288 0.334 691 560 706 570 41.20
500 0.0366 0.048 0.281 0.328 795 629 810 639 51.50
630 0.0283 0.040 0.274 0.320 911 702 925 709 64.89
800 0.0221 0.033 0.270 0.316 1022 769 1032 772 82.40

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information