N2XKY 1 x (16-800) mm² 0.6/1 kV

Cu / XLPE / LS / PVC
(Copper Conductor, XLPE Insulated, Lead Sheathed, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For indoors, outdoors, in ground and in duct.
Mainly on chemical industries, refineries, petrol
stations and any other locations where there is
a risk that solvent, fuel and other chemicals may
penetrate and mechanical damage is not likely
to occur.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Heat Resistance
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated


Note :
Conductor Shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 800 sqmm supplied in non compacted circular stranded (rm) or compacted circular stranded (cm) conductor shape

Standard Packing
16 - 185 sqmm supplied in wooden drum @ 1000 m
240 - 800 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
16
17.7 946
25
17.7 1,011
35
17.7 1,084
50
18.9 1,256
70
21.0 1,552
95
23.0 1,886
120
25.0 2,283
150
27.0 2,656
185
30.0 3,271
240
33.5 4,119
300
36.0 4,804
400
40.0 6,029
500 44.5 7,503
630 49.5 9,464
800 55.0 11,710

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
Trefoil formation
Flat formation
in air in ground in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) (mH/km) Max. (A) Max. (A) Max. (A) Max. (A) Max. (kA)
16
1.15 1.466 0.439 0.486 120 117 123 120 2.29
25
0.727 0.927 0.391 0.437 158 153 162 157 3.58
35
0.524 0.668 0.361 0.407 191 183 196 188 5.01
50
0.387 0.494 0.337 0.383 231 218 238 224 7.15
70
0.268 0.342 0.322 0.368 291 267 299 274 10.01
95
0.193 0.247 0.310 0.356 356 319 367 327 13.59
120
0.153 0.196 0.303 0.349 415 363 427 372 17.16
150
0.124 0.159 0.299 0.346 474 406 488 417 21.45
185
0.0991 0.128 0.296 0.342 550 459 565 471 26.46
240
0.0754 0.098 0.288 0.335 654 531 672 544 34.32
300
0.0601 0.079 0.282 0.328 752 598 771 611 42.90
400
0.0470 0.064 0.281 0.327 870 675 891 689 57.20
500 0.0366 0.051 0.276 0.322 1005 760 1026 772 71.50
630 0.0283 0.042 0.271 0.317 1155 849 1175 860 90.09
800 0.0221 0.035 0.269 0.315 1299 933 1315 939 114.40

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information