NYCY 5 x (1.5-50) mm2 0.6/1 kV

Cu / PVC / CWS / PVC
(Copper Conductor, PVC Insulated, Copper Wire Screen, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For installation in the ground, indoors, cable
trunking and outdoors if subsequent mechanical
damage is likely. For urban networks, household
feeders and street lighting.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Heat Resistance
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 50 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
1.5 - 50 sqmm supplied in wooden drum @ 1000 m
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
1.5/1.5 15.7 323
2.5/2.5 17.0 401
4/4 19.6 560
6/6 21.5 712
10/10 24.0 1,020
16/16 27.0 1,431
25/16 31.5 2,007
35/16 34.0 2,576
50/25 39.5 3,380

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 70°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
1.5/1.5 12.1 14.478 0.328 24 28 0.17
2.5/2.5 7.41 8.866 0.304 31 37 0.29
4/4 4.61 5.516 0.303 42 48 0.46
6/6 3.08 3.685 0.288 53 60 0.69
10/10 1.83 2.190 0.269 73 79 1.15
16/16 1.15 1.376 0.255 97 103 1.84
25/16 0.727 0.870 0.255 129 132 2.88
35/16 0.524 0.627 0.246 158 158 4.03
50/25 0.387 0.464 0.247 192 186 5.75

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information