NYM 5 x (1.5 - 35) mm² 300/500 V

Cu / PVC / PVC
(Copper Conductor, PVC Insulated, PVC Sheathed)
Standard Specification : IEC 60227-4 : 1997

Application

For building wire installed in conduit in dry
location and interwiring in switch board and
control panel, inherently fame retardant in
compliance with IEC 60332-1.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• Flame Retardant Cat. A, B, C
• Heat Resistance
• Nylon Coated


Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 - 35 sqmm supplied in non compacted circular stranded (rm) conductor shape

Standard Packing
1.5 - 2.5 sqmm supplied in coil @ 100 m or in wooden drum @ 1000/2000 m
4 - 35 sqmm supplied in wooden drum @ 1000 m
Length tolerance per drum ±2%.

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
1.5 11.5 198
2.5 13.0 278
4 15.0 400
6 16.5 524
10 20.0 805
16 25.0 1,274
25 30.0 1,927
35 33.5 2,514

Electrical Data

Conductor Insulation Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 70°C
Insulation
Resistance
at 70°C
in air
(mm²)
Max. (Ω/km)
Max. (Ω/km)
Min.
(M.Ω.km)
(mH/km) Max. (A) Max. (kA)
1.5 12.1 14.478 0.010 0.329 19 0.17
2.5 7.41 8.866 0.009 0.318 25 0.29
4 4.61 5.516 0.0077 0.297 34 0.46
6 3.08 3.685 0.0065 0.281 44 0.69
10 1.83 2.190 0.0065 0.278 61 1.15
16 1.15 1.376 0.0052 0.255 82 1.84
25 0.727 0.870 0.0050 0.252 108 2.88
35 0.524 0.627 0.0044 0.244 134 4.03

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information