NYSY 2 x (1.5-300) mm² 0.6/1 kV

Cu / PVC / CTS / PVC
(Copper Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For power plants and switchgear as well as
for installation of sub-station; for installation
indoors in confinned spaces and cable channels
because of small bending radius. As burried
cable, because of its light weight prefered in
where installation is difficult.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Heat Resistance
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated


Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
1.5 - 120 sqmm supplied in wooden drum @ 1000 m
150 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
1.5 12.2 206
2.5 13.2 249
4 15.1 336
6 16.3 405
10 18.2 543
16 20.5 716
25 23.5 1,001
35 26.0 1,270
50 29.0 1,565
70 33.0 2,099
95 37.5 2,821
120 40.5 3,409
150 45.0 4,176
185 50.0 5,169
240 56.0 6,627
300 62.0 8,203

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 70°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
1.5 12.1 14.478 0.328 23 28 0.17
2.5 7.41 8.866 0.304 31 37 0.29
4 4.61 5.516 0.303 41 48 0.46
6 3.08 3.685 0.288 52 60 0.69
10 1.83 2.190 0.269 71 81 1.15
16 1.15 1.376 0.255 94 105 1.84
25 0.727 0.870 0.255 123 135 2.88
35 0.524 0.627 0.246 152 163 4.03
50 0.387 0.464 0.247 183 193 5.75
70 0.268 0.321 0.238 231 238 8.05
95 0.193 0.232 0.238 282 283 10.93
120 0.153 0.184 0.233 327 323 13.80
150 0.124 0.150 0.233 373 362 17.25
185 0.0991 0.121 0.233 426 407 21.28
240 0.0754 0.093 0.232 502 470 27.60
300 0.0601 0.075 0.231 572 527 34.50

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information