NYSY 5 x (1.5-50) mm² 0.6/1 kV

Cu / PVC / CTS / PVC
(Copper Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For power plants and switchgear as well as
for installation of sub-station; for installation
indoors in confinned spaces and cable channels
because of small bending radius. As burried
cable, because of its light weight prefered in
where installation is difficult.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Heat Resistance
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated


Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 50 sqmm supplied in compacted circular stranded (cm) conductor shape


Standard Packing
1.5 - 50 sqmm supplied in wooden drum @ 1000 m
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
1.5 14.6 311
2.5 15.8 393
4 18.5 552
6 20.0 688
10 23.0 966
16 25.5 1,321
25 29.5 1,906
35 33.0 2,488
50 38.0 3,213

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 70°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
1.5 12.1 14.478 0.328 23 28 0.17
2.5 7.41 8.866 0.304 30 36 0.29
4 4.61 5.516 0.303 41 48 0.46
6 3.08 3.685 0.288 52 59 0.69
10 1.83 2.190 0.269 71 79 1.15
16 1.15 1.376 0.255 95 102 1.84
25 0.727 0.870 0.255 127 132 2.88
35 0.524 0.627 0.246 156 158 4.03
50 0.387 0.464 0.247 190 186 5.75

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information