NYY 5 x (1.5-50) mm² 0.6/1 kV

Cu / PVC / PVC
(Copper Conductor, PVC Insulated, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

Power cable : Indoors, cable trunking, outdoors
and burried in the ground, for power stations,
industry and switchgear as well as for urban
supply networks, if mechanical damage is
unlikely.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Heat Resistance
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated


Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 50 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
1.5 - 50 sqmm supplied in wooden drum @ 1000 m
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
1.5 14.8 302
2.5 16.0 382
4 18.7 541
6 20.5 677
10 23.0 954
16 26.0 1,309
25 30.0 1,895
35 33.0 2,478
50 38.0 3,161

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 70°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
1.5 12.1 14.478 0.328 23 27 0.17
2.5 7.41 8.866 0.304 30 36 0.29
4 4.61 5.516 0.303 41 47 0.46
6 3.08 3.685 0.288 52 59 0.69
10 1.83 2.190 0.269 71 78 1.15
16 1.15 1.376 0.255 94 101 1.84
25 0.727 0.870 0.255 126 131 2.88
35 0.524 0.627 0.246 155 157 4.03
50 0.387 0.464 0.247 189 185 5.75

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information