N2XBY 2 x (1.5-300) mm² 0.6/1 kV

Cu / XLPE / STA / PVC
(Copper Conductor, XLPE Insulated, Galvanized Steel Tape Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For installation indoors, cable channels and in
ground, for industry installations, switchgear,
and power station, if there is a risk that low
mechanical damage may occur.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
1.5 - 120 sqmm supplied in wooden drum @ 1000 m
150 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
1.5 14.4 293
2.5 14.4 310
4 14.4 328
6 15.4 397
10 17.4 533
16 19.4 705
25 22.5 986
35 25.0 1,252
50 28.0 1,529
70 32.0 2,081
95 35.5 2,739
120 40.5 3,726
150 45.0 4,518
185 50.0 5,537
240 55.5 6,987
300 61.0 8,514

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
1.5 12.1 15.429 0.328 29 34 0.21
2.5 7.41 9.449 0.304 39 45 0.36
4 4.61 5.878 0.275 51 59 0.57
6 3.08 3.927 0.263 65 74 0.86
10 1.83 2.334 0.248 89 100 1.43
16 1.15 1.467 0.238 118 130 2.29
25 0.727 0.927 0.240 157 167 3.58
35 0.524 0.669 0.233 193 201 5.01
50 0.387 0.494 0.232 233 239 7.15
70 0.268 0.342 0.229 295 293 10.01
95 0.193 0.247 0.224 360 350 13.59
120 0.153 0.196 0.223 423 401 17.16
150 0.124 0.160 0.224 482 449 21.45
185 0.0991 0.128 0.225 551 505 26.46
240 0.0754 0.099 0.223 652 584 34.32
300 0.0601 0.080 0.221 744 656 42.90

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information