N2XBY 3 x (1.5-300) mm² 0.6/1 kV

Cu / XLPE / STA / PVC
(Copper Conductor, XLPE Insulated, Galvanized Steel Tape Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For installation indoors, cable channels and in
ground, for industry installations, switchgear,
and power station, if there is a risk that low
mechanical damage may occur.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor

Standard Packing
1.5 - 95 sqmm supplied in wooden drum @ 1000 m
120 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
1.5 14.4 304
2.5 14.4 324
4 15.0 377
6 16.2 463
10 18.2 638
16 20.5 860
25 24.0 1,223
35 26.5 1,574
50 28.5 1,818
70 32.5 2,518
95 36.0 3,335
120 41.0 4,451
150 45.5 5,449
185 50.0 6,656
240 56.0 8,514
300 61.0 10,375

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
1.5 12.1 15.429 0.328 25 29 0.21
2.5 7.41 9.449 0.293 33 38 0.36
4 4.61 5.878 0.275 43 50 0.57
6 3.08 3.927 0.263 55 62 0.86
10 1.83 2.334 0.248 75 84 1.43
16 1.15 1.467 0.238 100 109 2.29
25 0.727 0.927 0.240 133 140 3.58
35 0.524 0.669 0.233 164 169 5.01
50 0.387 0.494 0.232 202 205 7.15
70 0.268 0.342 0.229 255 250 10.01
95 0.193 0.247 0.224 312 299 13.59
120 0.153 0.196 0.223 366 342 17.16
150 0.124 0.160 0.224 418 382 21.45
185 0.0991 0.128 0.225 483 433 26.46
240 0.0754 0.099 0.223 569 499 34.32
300 0.0601 0.080 0.221 652 561 42.90

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information