N2XBY 4 x (1.5-300) mm² 0.6/1 kV

Cu / XLPE / STA / PVC
(Copper Conductor, XLPE Insulated, Galvanized Steel Tape Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For installation indoors, cable channels and in
ground, for industry installations, switchgear,
and power station, if there is a risk that low
mechanical damage may occur.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor

Standard Packing
1.5 - 70 sqmm supplied in wooden drum @ 1000 m
95 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
1.5 14.4 310
2.5 14.7 347
4 16.0 440
6 17.4 548
10 19.7 773
16 22.5 1,055
25 26.0 1,517
35 29.0 1,967
50 32.5 2,356
70 37.0 3,260
95 42.5 4,727
120 47.5 5,823
150 53.5 7,104
185 57.5 8,651
240 64.0 11,087
300 69.5 13,530

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
1.5 12.1 15.429 0.315 27 32 0.21
2.5 7.41 9.449 0.293 36 42 0.36
4 4.61 5.878 0.275 48 55 0.57
6 3.08 3.927 0.263 60 68 0.86
10 1.83 2.334 0.248 83 91 1.43
16 1.15 1.467 0.238 110 118 2.29
25 0.727 0.927 0.240 148 152 3.58
35 0.524 0.669 0.233 183 183 5.01
50 0.387 0.494 0.232 214 210 7.15
70 0.268 0.342 0.229 269 256 10.01
95 0.193 0.247 0.224 334 309 13.59
120 0.153 0.196 0.223 386 350 17.16
150 0.124 0.160 0.224 449 395 21.45
185 0.0991 0.128 0.225 512 444 26.46
240 0.0754 0.099 0.223 604 513 34.32
300 0.0601 0.080 0.221 692 577 42.90

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information