N2XBY 5 x (1.5-50) mm² 0.6/1 kV

Cu / XLPE / STA / PVC
(Copper Conductor, XLPE Insulated, Galvanized Steel Tape Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For installation indoors, cable channels and in
ground, for industry installations, switchgear,
and power station, if there is a risk that low
mechanical damage may occur.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 50 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
1.5 - 50 sqmm supplied in wooden drum @ 1000 m
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
1.5 14.4 322
2.5 15.7 403
4 17.2 517
6 18.7 649
10 21.5 919
16 24.5 1,265
25 28.5 1,833
35 32.0 2,403
50 36.0 3,069

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
1.5 12.1 15.429 0.315 28 33 0.21
2.5 7.41 9.449 0.293 37 43 0.36
4 4.61 5.878 0.275 49 55 0.57
6 3.08 3.927 0.263 62 69 0.86
10 1.83 2.334 0.248 86 92 1.43
16 1.15 1.467 0.238 114 120 2.29
25 0.727 0.927 0.240 154 155 3.58
35 0.524 0.669 0.233 190 186 5.01
50 0.387 0.494 0.232 230 219 7.15

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information