N2XCY 2 x (1.5-300) mm² 0.6/1 kV

Cu / XLPE / CWS / PVC
(Copper Conductor, XLPE Insulated, Copper Wire Screen, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For installation in the ground, indoors, cable
trunking and outdoors if subsequent mechanical
damage is likely. For urban networks, household
feeders and street lighting.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
1.5 - 120 sqmm supplied in wooden drum @ 1000 m
150 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
1.5 / 1.5 13.0 198
2.5 / 2.5 13.9 239
4 / 4 15.0 304
6 / 6 16.2 384
10 / 10 18.1 546
16 / 16 21.0 766
25 / 16 24.0 1,030
35 / 16 26.0 1,283
50 / 25 29.5 1,631
70 / 35 33.0 2,247
95 / 50 37.5 3,028
120 / 70 42.0 3,817
150 / 70 46.0 4,526
185 / 95 51.0 5,694
240 / 120 57.0 7,302
300 / 150 63.0 9,049

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
1.5 / 1.5 12.1 15.429 0.315 30 35 0.21
2.5 / 2.5 7.41 9.449 0.293 39 46 0.36
4 / 4 4.61 5.878 0.275 52 60 0.57
6 / 6 3.08 3.927 0.263 66 75 0.86
10 / 10 1.83 2.334 0.248 90 100 1.43
16 / 16 1.15 1.467 0.238 120 131 2.29
25 / 16 0.727 0.927 0.240 159 168 3.58
35 / 16 0.524 0.669 0.233 195 203 5.01
50 / 25 0.387 0.494 0.232 238 241 7.15
70 / 35 0.268 0.342 0.229 299 295 10.01
95 / 50 0.193 0.247 0.224 365 352 13.59
120 / 70 0.153 0.196 0.223 425 400 17.16
150 / 70 0.124 0.160 0.224 484 448 21.45
185 / 95 0.0991 0.128 0.225 552 502 26.46
240 / 120 0.0754 0.099 0.223 650 578 34.32
300 / 150 0.0601 0.080 0.221 736 643 42.90

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information