N2XCY 5 x (1.5-50) mm2 0.6/1 kV

Cu / XLPE / CWS / PVC
(Copper Conductor, XLPE Insulated, Copper Wire Screen, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For installation in the ground, indoors, cable
trunking and outdoors if subsequent mechanical
damage is likely. For urban networks, household
feeders and street lighting.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 50 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
1.5 - 50 sqmm supplied in wooden drum @ 1000 m
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
1.5 / 1.5 15.2 291
2.5 / 2.5 16.4 365
4 / 4 17.9 476
6 / 6 19.5 617
10 / 10 22.5 909
16 / 16 25.5 1,300
25 / 16 29.5 1,844
35 / 16 32.5 2,390
50 / 25 37.0 3,120

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
1.5 / 1.5 12.1 15.429 0.315 29 33 0.21
2.5 / 2.5 7.41 9.449 0.293 38 43 0.36
4 / 4 4.61 5.878 0.275 50 56 0.57
6 / 6 3.08 3.927 0.263 63 70 0.86
10 / 10 1.83 2.334 0.248 87 93 1.43
16 / 16 1.15 1.467 0.238 116 120 2.29
25 / 16 0.727 0.927 0.240 156 156 3.58
35 / 16 0.524 0.669 0.233 191 186 5.01
50 / 25 0.387 0.494 0.232 231 218 7.15

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information