N2XFGbY 3 x (1.5-300) mm² 0.6/1 kV

Cu / XLPE / SFWA / PVC
(Copper Conductor, XLPE Insulated, Galvanized Steel Flat Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For installation in the ground, indoors, cable trunking and outdoors if increased mechanical protection is required or where high-pulling stresses may occur during installation or operation.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor

Standard Packing
1.5 - 95 sqmm supplied in wooden drum @ 1000 m
120 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
1.5 17.9 615
2.5 17.9 634
4 17.9 664
6 17.9 711
10 19.7 892
16 22.0 1,163
25 25.5 1,572
35 28.0 1,972
50 30.0 2,252
70 34.5 3,026
95 37.5 3,876
120 41.0 4,667
150 46.0 5,692
185 50.5 6,927
240 56.0 8,800
300 61.0 10,708

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
1.5 12.1 15.429 0.340 26 28 0.21
2.5 7.41 9.449 0.304 34 37 0.36
4 4.61 5.878 0.285 45 50 0.57
6 3.08 3.927 0.263 56 63 0.86
10 1.83 2.334 0.248 77 85 1.43
16 1.15 1.467 0.238 103 110 2.29
25 0.727 0.927 0.240 136 142 3.58
35 0.524 0.669 0.233 167 170 5.01
50 0.387 0.494 0.232 206 206 7.15
70 0.268 0.342 0.229 259 252 10.01
95 0.193 0.247 0.224 317 301 13.59
120 0.153 0.196 0.223 367 343 17.16
150 0.124 0.160 0.224 419 383 21.45
185 0.0991 0.128 0.225 484 433 26.46
240 0.0754 0.099 0.223 571 500 34.32
300 0.0601 0.080 0.221 654 563 42.90

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information