N2XFGbY 4 x (1.5-300) mm² 0.6/1 kV

Cu / XLPE / SFWA / PVC
(Copper Conductor, XLPE Insulated, Galvanized Steel Flat Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For installation in the ground, indoors, cable trunking and outdoors if increased mechanical protection is required or where high-pulling stresses may occur during installation or operation.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor

Standard Packing
1.5 - 70 sqmm supplied in wooden drum @ 1000 m
95 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
1.5 17.9 622
2.5 17.9 643
4 17.9 688
6 18.8 803
10 21.5 1,050
16 24.0 1,381
25 27.5 1,889
35 30.5 2,387
50 34.0 2,839
70 38.5 3,816
95 42.5 4,951
120 47.5 6,074
150 53.5 7,390
185 57.5 8,946
240 64.5 11,436
300 70.0 13,925

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
1.5 12.1 15.429 0.328 28 31 0.21
2.5 7.41 9.449 0.304 38 42 0.36
4 4.61 5.878 0.275 49 55 0.57
6 3.08 3.927 0.263 62 69 0.86
10 1.83 2.334 0.248 85 92 1.43
16 1.15 1.467 0.238 113 119 2.29
25 0.727 0.927 0.240 151 154 3.58
35 0.524 0.669 0.233 186 184 5.01
50 0.387 0.494 0.232 218 211 7.15
70 0.268 0.342 0.229 272 258 10.01
95 0.193 0.247 0.224 334 309 13.59
120 0.153 0.196 0.223 387 350 17.16
150 0.124 0.160 0.224 450 396 21.45
185 0.0991 0.128 0.225 513 445 26.46
240 0.0754 0.099 0.223 606 514 34.32
300 0.0601 0.080 0.221 694 578 42.90

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information